Run has the third highest operating priority. Run ramps to the scaled setpoint speed,
using the Acceleration Time (CP-16). Run can be activated when the MLP–Drive is in
R–Stop or F–Stop, however Run cannot be activated when the MLP–Drive is in Jog.
To activate Run:
Short the F–Stop and R–Stop inputs to common.
Open the Jog input.
Short the Run input to common. (Run is latched and does not need to be
maintained to remain active.)
R-STOP
F-STOP
RUN
JOG
R-STOP
F-STOP
COMMON
JOG
RUN
Close Momentarily
4
5
6
7
8
J5