Contrex ML-Drive Manual de usuario

Busca en linea o descarga Manual de usuario para Sensores Contrex ML-Drive. CONTREX ML-Drive User Manual [en] Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 178
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente

Indice de contenidos

Pagina 3

3 - 66Table 3-35 ASCII to Binary@ 1000000 ' 1100000A 1000001 a 1100001B 1000010 b 1100010C 1000011 c 1100011D 1000100 d 1100100E 1000101 e

Pagina 4

3 - 67Table 3-36 Binary to Monitor ParametersMP-50 MP-51 MP-52 MP-53 MP-54

Pagina 6

4 - 1TroubleshootingDiagnosticsTroubleshootingPROM Chip Replacement

Pagina 8 - List of Tables

4 - 3DIAGNOSTICSThis section describes how to use the diagnostic routines to verify that the ML-Drive isoperating properly as well as to identify any

Pagina 9 - Introduction

4 - 4RAM Test #1 - To Test Random Access MemoryClear/4 will automatically default to RAM Test #1. The diagnosticindicator and the number “1” will be

Pagina 10

4 - 5Display Test #2 - To Test the LED Display Panel SegmentsPress the “UP” or “DOWN” scroll keys until the diagnostic indicator andthe number “2” are

Pagina 11 - INTRODUCING THE ML-DRIVE

4 - 6Keypad Test #3 - To Test the KeypadPress the “UP” or “DOWN” scroll keys until the diagnostic indicator andthe number “3” are visible on the left

Pagina 12 - APPLICATIONS

4 - 7Input Test #4 - To Test the Logic InputsPress the “UP” or “DOWN” scroll keys until the diagnostic indicator andthe number “4” are visible on the

Pagina 13

1 - 3INTRODUCING THE ML-DRIVEThe ML-Drive is a highly accurate, digital, motor drive which can drive 1/4 to 2horsepower PM DC motors. It has advanced

Pagina 14

4 - 8Output Test #5 - To Test the Logic OutputsPress the “UP” or “DOWN” scroll keys until the diagnostic indicator andthe number “5” are visible on th

Pagina 15 - Installation / Setup

4 - 9In addition to diagnostic tests 1-5, the ML-Drive automatically performs two power updiagnostic routines during every Power Up.RAM TEST - Random

Pagina 16 - DOOR PANEL

4 - 10—NOTES—

Pagina 17 - MOUNTING

4 - 11TROUBLESHOOTINGThis section contains four troubleshooting flowcharts to help you resolve four possiblesystem operating problems. The four scena

Pagina 18

4 - 12Figure 4-1 Motor Does Not Stop FlowchartYesMotor Does Not StopMP-53 =1000 (F–Stop)J4, Pin 6 isshorted to commonMP-53 =0100 (R–Stop)MP-53 =0010

Pagina 19 - Hazardous voltages!

4 - 13MP-50 =0010(Master)MP-50 =0100(Follower)MP-50 =0001(Direct)YesMotor Does Not RunProblem CorrectedYesYesNoNoNoNoSetpoint is correct ?NoYesMP-45 i

Pagina 20

4 - 14Figure 4-3 Motor Runs at Wrong Speed FlowchartMP-50 =0010(Master)MP-50 =0100(Follower)MP-50 =0001(Direct)YesMotor Runs at Wrong SpeedProblem C

Pagina 21 - I/O Power (J4 pins 1, 2)

4 - 15Figure 4-4 Motor Runs Unstable FlowchartChange CP-61 to “1”and Run in Direct ModeNoMotor Runs UnstableMotor StillUnstable ?NoYesProblem Correc

Pagina 22 - Lead Frequency (J4 pins 3, 5)

4 - 16PROM CHIP REPLACEMENTThe PROM (Programmable Read Only Memory) chip is the software for the ML-Drive.See Figure 4-5 for the PROM's location

Pagina 23 - DANGER !

4 - 17Figure 4-5 PROM LocationBeveled CornerInsert Tool HereInsert Tool Here

Pagina 24 - R–Stop (J4 pins 9, 11)

1 - 4EXAMPLES OF ML-DRIVEAPPLICATIONSFigure 1-1 is an example of a Master mode of operation for a pump application. Thescaling format allows the oper

Pagina 26

Glossary - 1Glossary

Pagina 28 - Alarm (J4 pin 17)

Glossary - 3GLOSSARYAcceleration/Deceleration Acceleration Time (CP-16) and Deceleration Time (CP-17)control the rate of speed change in response to s

Pagina 29 - SERIAL COMMUNICATIONS

Glossary - 4the Follower mode, Acceleration/Deceleration, Tuning,Alarms, and Jog. The ML-Drive comes factory pre-loadedwith a complete set of default

Pagina 30 - — +

Glossary - 5Drive Enable The Drive Enable output is activated based on theRamped Reference (MP-46) and the feedback. TheRamped Reference is the calcu

Pagina 31 - CALIBRATION

Glossary - 6Input Monitoring Lead Frequency (MP-41)Feedback Frequency (MP-43)Logic Inputs, Group A (MP-54)Logic Inputs, Group B (MP-55)Input Test Test

Pagina 32 - CURRENT LIMIT

Glossary - 7Master Mode A stand-alone control of a single motor. The scaling formatallows the operator to enter a setpoint in EngineeringUnits. The

Pagina 33

Glossary - 8

Pagina 34

Glossary - 9Output Test Tests the Logic Outputs.Outputs Drive Out (J2 pins 1, 2)Drive Enable (J4 pin 16, 18)Alarm (J4 pin 17, 18)Parameters Parameters

Pagina 35 - Operation

1 - 5Figure 1-2 is an example of the Follower mode of operation in a pump application. Thescaling format allows the operator to enter the setpoint as

Pagina 36

Glossary - 10Tuning Tuning stabilizes speed error differences between thesetpoint and feedback.Ring Kits Ring Kits are flange motor mounted sensors th

Pagina 37 - KEYPAD OPERATION

AppendicesAppendix A - ML-Drive SpecificationsAppendix B - FormulasAppendix C - Parameter Summary -Numeric Quick ReferenceAppendix D - Control Paramet

Pagina 39 - KEYPAD LOCKOUT

A-1APPENDIX A: ML-DRIVE SPECIFICATIONSAccuracy: .01% Set SpeedResponse: 10 millisecond control loop updateTuning: Separately adjustable Gain, Integra

Pagina 40

A-2Digital Outputs: Open-Collector Driver (ULN2003)(50 VDC max, 200 mA continuous, 500 mA peak)Optically IsolatedDrive EnableAlarmDrive Output: Phase

Pagina 41 - CONTROL PARAMETERS

B - 1APPENDIX B: FORMULASUse the following formulas to calculate Speed Control:MASTER MODEGeneralHZRPMSetpointMaster = RPMFeedbackE.U.Master

Pagina 42

B - 2—NOTES—

Pagina 43

C - 1APPENDIX C: PARAMETER SUMMARY -NUMERIC QUICK REFERENCECP-01 MASTER SETPOINT 1The Engineering Units value that you want your system to operate at

Pagina 44 - CP-31 PPR Feedback 60

C - 2CP-06 DIRECT SETPOINTUse the Direct Setpoint (CP-06) to set the drive output that is used when the ML-Drive is in theDirect Mode of operation. D

Pagina 45

C - 3CP-15 SCALED ERROR ALARMThe Scaled Error Alarm (CP-15) is the RPM deviation between the scaled reference and thefeedback that will activate the A

Pagina 47

C - 4CP-31 PPR FEEDBACKPPR Feedback (CP-31) is the number of gear teeth or number of encoder lines on the Followerfeedback sensor per revolution (puls

Pagina 48

C - 5MP-43 FEEDBACK FREQUENCYThe Feedback Frequency (MP-43) displays the frequency of the Feedback Frequency Input(J4 pin 4) in units of hertz (pu

Pagina 49 - Setpoint Select

C - 6MP-47 DRIVE OUTPUTThe Drive Output (MP-47) displays the drive output level to the motor (J2 pin 1, 2). Drive Outputis displayed as a percentage;

Pagina 50

C - 7MP-51 KEYPAD ERRORIf a Control Parameter entry has been rejected, Keypad Error (MP-51) will ascertain the reasonthat it was rejected. Keypad E

Pagina 51

C - 8MP-53 CONTROL STATEControl State (MP-53 ) displays a number “1” to indicate the active control state of theML–Drive. In the example below, “Run

Pagina 52

C - 9MP-55 LOGIC INPUTS - GROUP BThe Logic Inputs - Group B (MP-55) displays the status of the Master/Follower and SetpointSelect logic inputs. The n

Pagina 53 - ___

C - 10MP-58 SERIAL COMMUNICATIONS ERRORSerial Communications Error (MP-58) identifies errors in the last transmitted message that wassent to the ML-Dr

Pagina 54

C - 11CP-62 INVERSE SCALINGUse Inverse Scaling (CP-61) to select either the Standard or the Inverse setpoint scaling format.Enter “2” for Inverse Scal

Pagina 55

C - 12CP-67 DERIVATIVEIn systems with a very large inertia, use Derivative (CP-67) to reduce the overshoot from theintegral term. Decrease the value

Pagina 56 - Inverse Master Mode

C - 13CP-73 CONTROL MASKThe Serial Communications can control some of the logic input functions. Enter the number forthe required functions in Contro

Pagina 57

2 - 1Installation / SetupMountingWiringInputsOutputsSerial CommunicationsCalibrationCurrent Limit

Pagina 58 - Inverse Follower Mode

C - 14MP-83 CURRENT LIMIT STATUSCurrent Limit Status (MP-83) displays the present status of the current limit. When the ML-Driveis current limiting,

Pagina 59

D - 1USERCODE DESCRIPTION MIN MAX DEFAULT RECORD UNITSCP-01 Master Setpoint 1 0000 9999 0000 ENGCP-02 Master Setpoint 2 0000 9999 0000 ENGCP-03 Follow

Pagina 61 - CP-68 Feedforward 1000

E - 1APPENDIX E: MONITOR PARAMETERREFERENCECODE DESCRIPTION MIN MAX UNITSMP-40 Tach 0 9999 ENG.MP-41 Lead Frequency 0 9999 HZMP-43 Feedback Frequency

Pagina 62

E- 2—NOTES—

Pagina 63 - Operations: Keypad

F - 1APPENDIX F: ML-DRIVE FAX COVER SHEETDate: ______________________Atten: Contrex Technical SupportFax Number: 1-763-424-8734From:Name ___________

Pagina 64

F - 2MP-53 Control StateMP-54 Logic Inputs - Group AMP-55 Logic Inputs - Group BMP-56 Logic OutputsMP-57 EEPROM StatusMP-58 Serial Comm ErrorMP-59 Fre

Pagina 65

G- 1APPENDIX G: WIRING DIAGRAMEXAMPLESDANGERThis diagram is for conceptual purposes only!Use safety equipment.Make wiring connections carefully.Incor

Pagina 66 - CP-05 Jog Setpoint

G - 2DANGERThis diagram is for conceptual purposes only!Use safety equipment.Make wiring connections carefully.Incorrect use of equipment or connectio

Pagina 67 - LOGIC CONTROL

G- 3Figure G-3 Start/Stop with Armature ContactorDANGERThis diagram is for conceptual purposes only!Use safety equipment.Make wiring connections care

Pagina 68 - Logic Inputs

2 - 2Figure 2-1 ML-Drive Cutout Dimensions and Mounting Guide3.60"3.60"4.00"*6.00"4.00"DOOR PANEL(3.65" .03" CUT

Pagina 69

G - 4DANGERThis diagram is for conceptual purposes only!Use safety equipment.Make wiring connections carefully.Incorrect use of equipment or connectio

Pagina 70

E ---04/13---Update Page 2-5 for Motor Over-temp protection

Pagina 72

Warranty - 1WarrantyService PolicyWarranty

Pagina 74 - Input Monitoring

Warranty - 3SERVICE POLICYContrex, Inc., recognizes that with each saleof its product there are certain productobligations. This document defines th

Pagina 75 - F–Stop (J4 Pin 10)

Warranty - 4WARRANTYContrex, Inc., guarantees this device againstdefects in workmanship and materials for aperiod of one (1) year from the date ofpurc

Pagina 76 - Not Used

Index - 1Index

Pagina 78

Index - 3IndexAAC Power (J2 pins 3, 4, 5)..page 2-8Acceleration Time..page 3-26, 3-32, C-3, D-1Acceleration/Deceleration..page 3-26, Glossary-3Active

Pagina 79 - Status Monitoring

2 - 3MOUNTINGThis section contains instructions for mounting the ML-Drive in the door panel of aNEMA Industrial Electrical enclosure. The ML-Drive is

Pagina 80 - Scaled Error

Index - 4Control Parameters..page 3-7, Glossary-3CP-01..page 3-9, 3-10, 3-11, 3-23, C-1, D-1CP-02..page 3-9, 3-10, 3-11, 3-23, C-1, D-1CP-03..page 3-1

Pagina 81

Index - 5Dedicated Keys.See Keys: DedicatedDerivative..page 3-27, C-12, D-1Deviation..page 3-29, 3-43, C-2, C-5, E-1Device Address..page 3-50, C-12, D

Pagina 82

Index - 6HHardwired..page Glossary-5High Alarm..page 3-29, 3-46, C-2, D-1Host Computer, Interface..page 3-49, 3-52Housing the ML-Drive..page 2-3How to

Pagina 83

Index - 7J4 pins 9, 11 (R–Stop)..page 2-10Jog..page 3-32, 3-36, Glossary-6Jog input (J4 pins 7, 8)..page 2-10Jog Setpoint..page 3-32, C-1, D-1KKeypadB

Pagina 84 - Using Serial Communications

Index - 8Master Setpoint 2..page 3-9, C-1, D-1Max RPM Feedback..page 3-9, 3-13, C-4, D-1Max RPM Lead..page 3-13, C-4, D-1ML-DriveExample of Applicatio

Pagina 85 - Control Mask Error

Index - 9OOpen Loop..page 1-3, Glossary-7Operating State..page Glossary-7Operating StatesF–Stop..page 3-34Jog..page 3-36R–Stop..page 3-34Run..page 3-3

Pagina 86

Index - 10Send..page 3-53, Glossary-9Summary Reference List..page C-1Value..page 3-7, 3-39, Glossary-9Peak Current Limit.See Current Limit: PeakPerfor

Pagina 87 - Characters 2, 3 - Device #:

Index - 11Setpoint Select Input (J4 pins 13, 14)..page 2-12SetupCalibration..page 2-17Mounting the ML-Drive..page 2-3Wiring..page 2-5SoftwareCode Revi

Pagina 88

Index - 12—NOTES—

Pagina 89 - Example of Parameter Send:

2 - 4Figure 2-2 ML-Drive General Wiring5V_DICOMLEAD_FQFDBK_FQCOMRUNJOGCOMR–STOPF–STOPCOMMST / FOLSETPTCOMV_DODRV_ENALARMCOMUSE COPPER WIRE ONLY. SEL

Pagina 90 - Character 4 - Error Code:

WIRINGThis section contains the power supply, input, and output wiring for the ML-Drive. Please read this section prior to wiring

Pagina 91 - Character 11 - Data Format:

iiTechnical AssistanceIf you have comments or questions concerning the operation of the ML-Drive, please call. A member of our Technical Support Staff

Pagina 93 - Characters 9,10- DATA:

2 - 7Figure 2-3 I/O Power / IsolatedFigure 2-4 I/O Power / Non-IsolatedINPUTSNOTE: The installation of this motor control must conform to area an

Pagina 94

2 - 8AC Power (J2 pins 3, 4, 5)The ML–Drive model #3200-1933operates on 115 VAC + 15%, 0.1Amp., 50/60 Hz. The ML–Drive model#3200-1934 operates on 23

Pagina 95

2 - 9Feedback Frequency(J4 pins 4, 5)The Feedback Frequency is a pulsetrain input that the ML-Drive uses todetermine the speed of the followermotor.

Pagina 96 - Data Inquiry

2 - 10Figure 2-9 JogFigure 2-10 R–StopJOG78J4R-STOP911J4Jog (J4 pins 7, 8)Jog is a maintained input. When Jogis closed, the ML-Drive commandsthe

Pagina 97

2 - 11Figure 2-11 F–StopF–Stop (J4 pins 10, 11)F–Stop is a momentary input. Whenit is open, the ML-Drive stopsimmediately (zero RPM) and ignoresthe

Pagina 98 - Character 4 -Error Code:

2 - 12Figure 2-13 Setpoint SelectSetpoint Select (J4 pins 13, 14)The Master and Follower setpointsare determined by the Setpoint Selectinput combine

Pagina 99 - 6 -XX.XX

2 - 13OUTPUTSNOTE: The installation of this motor control must conform to area and local electricalcodes. See The National Electrical Code (NEC,) Art

Pagina 100 - Table 3-35 ASCII to Binary

2 - 14Alarm (J4 pin 17)By entering alarm Control Parameters, you can establish circumstances under whichthe ML-Drive will alert you to potential oper

Pagina 101 - Setpoint

2 - 15Figure 2-16 ML-Drive Multidrop InstallationSERIAL COMMUNICATIONSNOTE: The installation of this motor control must conform to area and local el

Pagina 102

iiiDANGERImproper installation cancause severe injury, death ordamage to your system.Integrate this motion controlunit into your system withcaution.Op

Pagina 103 - Troubleshooting

2 - 16Figure 2-17 ML-Drive Serial Communications Connections1. Shield only at one end of the cable.2. If you need to terminate the communication lin

Pagina 104

2 - 17CALIBRATIONCalibration sets the ML-Drive's current limit. The ML-Drive must be properly installedprior to calibration. Refer to Installat

Pagina 105 - Test Number

2 - 18CURRENT LIMITThe ML-Drive provides current limiting for both RMS continuous duty and RMS peakintermittent duty. The RMS current limit level is

Pagina 106

2 - 19Use Motor Current (MP-82) to display the value, in amps, of the motor armature'scurrent:Press “Code Select”Enter “82” (Motor Current)Press

Pagina 107

2 - 20—NOTES—

Pagina 108

3 - 1OperationKeypad OperationKeypad LockoutControl Parameters (CP)Direct ModeMaster ModeFollower ModeInverse Master ModeInverse Follower ModeAccelera

Pagina 110 - 1 Drive Enable

3 - 3KEYPAD OPERATIONThe front panel of the ML-Drive is an easy to use keypad that gives you direct accessto the Parameters (Control Parameters and Mo

Pagina 111 - PROM TEST

3 - 4Press “Code Select”.Enter a Parameter Code (For a Control Parameter or Monitor Parameter).Press “Enter” (within 15 seconds).The Parameter Code an

Pagina 112

3 - 5KEYPAD LOCKOUTKeypad Lockout (CP-98) displays the present status of the keypad lockout. When thekeypad is locked, then “LOC” is displayed:Locked

Pagina 114 - Motor Does Not Stop

3 - 6Record your numeric Keypad Lockout password here:Please read the “CAUTION” statement on Page 3-5

Pagina 115 - 1-800-342-4411

3 - 7CONTROL PARAMETERSParameters are divided into two classifications; Control Parameters (CP) and MonitorParameters (MP). The numbered code that re

Pagina 116 - Motor Runs at Wrong Speed

3 - 8Direct ModeIn the Direct mode of operation, the drive output from the ML-Drive to the motor can beset directly. Direct mode is an open-loop mode

Pagina 117 - Motor Runs Unstable

3 - 9Master ModeThe Master, or stand-alone mode of operation, is a single motor operation. In thissimple mode of operation, the entire process is con

Pagina 118 - PROM CHIP REPLACEMENT

3 - 10Table 3-4 Default Master Scaling Control ParametersCP Parameter Name Parameter ValueCP-34 Max RPM Feedback 2000CP-31 PPR Feedback 60CP-20 Mas

Pagina 119 - Insert Tool Here

3 - 11Table 3-6 Entering Master Setpoint Control ParametersCP Parameter Name Parameter ValueCP-01 Master Setpoint 1 CP-02 Master Setpoint 2Enter the

Pagina 120

3 - 12 Master Mode ExampleThe following example demonstrates how scaling and setpoint Control Parameters areentered for a typical Master mode of opera

Pagina 121 - Glossary

3 - 13Follower ModeThe Follower mode of operation is the most frequently used mode of operation. It is amulti-motor operation in which the entire pro

Pagina 122 - Glossary - 2

3 - 14Table 3-8 Default Follower Scaling Control ParametersCP Parameter Name Parameter ValueCP-33 Max RPM Lead 2000CP-34 Max RPM Feedback 2000CP-30

Pagina 123 - GLOSSARY

3 - 15With your scaling established, you can enter values for Follower Setpoints 1 and 2(CP-03, CP-04). The value that you enter for a setpoint is t

Pagina 124 - Glossary - 4

vTable of ContentsIntroduction... 1-1Introducing the ML-Drive ...

Pagina 125 - Glossary - 5

3 - 16Follower Mode Examples A and BExample A demonstrates how scaling and setpoint Control Parameters are entered fora typical Follower mode of opera

Pagina 126 - Glossary - 6

3 - 17To find Follower Setpoint 1 (CP-03) for Example A:Follower E.U. desired 15Setpoint 1 =________________________________=___=3Lead E.U. operatio

Pagina 127 - Glossary - 7

3 - 18Table 3-11 Follower Mode Control Parameters Example ACP Parameter Name Parameter ValueCP-33 Max RPM Lead 1725CP-34 Max RPM Feedback 1800CP-30

Pagina 128 - Glossary - 8

3 - 19Example B demonstrates how scaling and setpoint Control Parameters are entered fora typical Follower mode of operation that uses a percentage se

Pagina 129 - Glossary - 9

3 - 20To find Follower Setpoint 1 (CP-03) for Example B:Follower E.U. desiredSetpoint 1 =________________________________x 100 (%)Lead E.U. operatio

Pagina 130 - Glossary - 10

3 - 21Table 3-12 Follower Mode Control Parameters Example BCP Parameter Name Parameter ValueCP-33 Max RPM Lead 1800CP-34 Max RPM Feedback 1800CP-30 P

Pagina 131 - Appendices

3 - 22Inverse Master ModeThe Inverse Master Mode is a variation of the Master Mode. The Inverse Master Modehas an inverted setpoint. If you increase

Pagina 132

3 - 23Inverse Master Mode ExampleThe Inverse Master Mode Example demonstrates how scaling and setpoint ControlParameters are entered for a typical Inv

Pagina 133

3 - 24Inverse Follower ModeThe Inverse Follower Mode is a variation of the Follower Mode. The Inverse FollowerMode has an inverted setpoint. If you

Pagina 134

3 - 25Inverse Follower Mode ExampleThe Inverse Follower Mode Example demonstrates how the scaling and setpointControl Parameters are entered for a typ

Pagina 135

viMonitor Parameters ... 3-39Input Monitoring ...

Pagina 136

3 - 26Acceleration/DecelerationAcceleration/Deceleration (CP-16 and CP-17) control the rate of speed change inresponse to setpoint changes. These par

Pagina 137 - NUMERIC QUICK REFERENCE

3 - 27TuningIf your system is unstable, or the speed error is unacceptable, tuning stabilizes speederror differences between the setpoint and feedback

Pagina 138 - CP-14 RAMPED ERROR ALARM

3 - 28Table 3-22 Entering Master / Follower Tuning Control ParametersCP Parameter Name Parameter ValueCP-65 Gain (Proportional)CP-66 IntegralCP-67

Pagina 139

3 - 29AlarmsThe Control Parameters for Alarms are identical for both the Master and the Followermodes of operations. By entering values in the Contro

Pagina 140 - MP-41 LEAD FREQUENCY

3 - 30Table 3-23 Default Alarms Control ParametersCP Parameter Name Parameter ValueCP-10 Alarm Format 15CP-12 Low Alarm 0CP-13 High Alarm 2000CP-14 R

Pagina 141 - MP-46 RAMPED REFERENCE

3 - 31Table 3-24 Entering Alarms Control ParametersCP Parameter Name Parameter ValueEnter the RPMs at or below which you want the Alarm output to act

Pagina 142 - Follower Mode

3 - 32JogJog increases the RPMs at the acceleration rate that you specified in Acceleration Time(CP-16) until the Jog Setpoint (CP-05) is achieved. W

Pagina 143 - Entry Timeout

3 - 33LOGIC CONTROLThis section addresses the four digital inputs that control the ML-Drive's operatingstate. Logic Control also addresses one d

Pagina 144 - MP-54 LOGIC INPUTS - GROUP A

3 - 34Logic InputsF–Stop has priority over the other operating states. F–Stop brings the ML-Drive's driveoutput to an immediate Zero.To activate

Pagina 145 - MP-57 EEPROM STATUS

3 - 35Run has the third highest operating priority. Run ramps to the scaled setpoint speed,using the Acceleration Time (CP-16). Run can be activated

Pagina 146 - CP-61 DIRECT ENABLE

viiList of IllustrationsFigure 1-1 ML-Drive Master Mode ... 1-4Figure 1-2 ML-Drive Follower M

Pagina 147 - Inverse Scaling

3 - 36Jog has the least operating priority. Jog ramps to the Jog Setpoint (CP-05), using theAcceleration Time (CP-16). When Jog is terminated, the M

Pagina 148 - CP-72 CHARACTER FORMAT

3 - 37Logic OutputThe Drive Enable output is controlled by the Ramped Reference (MP-46) and thefeedback. Drive Enable Logic (CP-74) determines which

Pagina 150 - MP-00 SOFTWARE PART NUMBER

3 - 39MONITOR PARAMETERSParameters are divided into two classifications; Control Parameters (CP) and MonitorParameters (MP). The numbered code that r

Pagina 151 - REFERENCE

3 - 40Input MonitoringThese MPs monitor the ML-Drive's inputs.MP-41 LEAD FREQUENCYThe Lead Frequency (MP-41) displays the frequency of the Le

Pagina 152

3 - 41MP-54 LOGIC INPUTS - GROUP AThe Logic Inputs - Group A (MP-54) displays the status of the Run, Jog, R–Stop and F–Stop digital inputs. The n

Pagina 153

3 - 42Output MonitoringThese MPs monitor the ML-Drive's outputs.MP-47 DRIVE OUTPUTThe Drive Output (MP-47) displays the drive output to the motor

Pagina 154

3 - 43Performance MonitoringPerformance Monitor Parameters monitor the performance of the ML-Drive and yoursystem. Figure 3-2 is a block diagram of t

Pagina 155 - 1-763-424-8734

3 - 44MP-45 SCALED REFERENCEThe Scaled Reference (MP-45) is the scaled setpoint number converted to hertz. It isthe calculated value that is inpu

Pagina 156

3 - 45Status MonitoringThese MPs monitor the status of the ML-Drive's modes of operation and operatingstates.MP-50 ACTIVE SCALING MODEThe digi

Pagina 157 - Use safety equipment

viiiList of TablesTable 3-1 Basic Keypad Entry ... 3-4Table 3-2 Default Direct Mode Cont

Pagina 158

3 - 46MP-52 ALARM STATUSThe digit that displays a number “1” is the active Alarm. In the example below, “HighSpeed Alarm ” is the active alarm.Lo

Pagina 159

3 - 47MP-59 FREQUENCY OVERFLOW COUNTERThe Frequency Overflow Counter (MP-59) is a counter that increments each time thefrequency input to the ML-Drive

Pagina 160

3 - 48—NOTES—

Pagina 161

3 - 49SERIAL COMMUNICATIONSThe ML-Drive can interface with a host computer through a RS485 SerialCommunications Interface. This interface allows the

Pagina 162

3 - 50Using Serial CommunicationsThis section describes how to use the Serial Communications. Before you can applythis section, The ML-Drive must be

Pagina 163 - Warranty

3 - 51CP-72 CHARACTER FORMATThe ML-Drive uses three different character formats. Enter the number for the requiredformat, as listed below.1 = 8 D

Pagina 164 - Warranty - 2

3 - 52Communications Software DesignThe ML-Drive Serial Communications Interface uses a polling technique to establish alink with the host computer.

Pagina 165 - Service

3 - 53Parameter SendUse the Parameter Send to change any of the ML-Drive's Control Parameters.Table 3-29 Parameter Send - Host TransmissionChar

Pagina 166 - WARRANTY

3 - 54Character 4 - Message Type:This character should always be “3”.Character 5, 6 - Parameter Number:These characters identify the Control Parameter

Pagina 167 - Index - 1

3 - 55Character 12 - ETX:Always use the ASCII “ETX” character to terminate the character string.Example of Parameter Send:A new Acceleration Time of 5

Pagina 168 - Index - 2

1 - 1IntroductionIntroducing the ML-DriveExamples of ML-Drive Applications

Pagina 169 - Index - 3

3 - 56Table 3-30 Parameter Send - ML-Drive ResponseCharacter # 1 2 3 4 5 6 7 8 9 10 11 12DEV # DEV # ERROR PAR # PAR # DATA DATA DATA DATA DATADESC

Pagina 170 - Index - 4

3 - 57Characters 5,6 - Parameter Number:The Control Parameter code is sent back to the host computer from the ML-Drive.Characters 7 through 10 - DATA:

Pagina 171 - Index - 5

3 - 58Control Command SendThe Control Command Send allows the host computer to control the operatingfunctions of the ML-Drive that are associated with

Pagina 172 - Index - 6

3 - 59Characters 5,6 - Parameter Number:These characters should always be “0”.Characters 7 through 8 - DATA:These characters should always be “0”.Char

Pagina 173 - Index - 7

3 - 60Table 3-32 Control Command Send - ML-Drive ResponseCharacter # 1 2 3 4 5 6 7 8 9 10 11 12DEV # DEV # ERROR PAR # PAR # DATA DATA DATA DATA DAT

Pagina 174 - Index - 8

3 - 61Characters 5,6 - Parameter Number:These characters will always be “0”.Characters 7 through 10 - DATA:These characters will always be “0”.Charact

Pagina 175 - Index - 9

3 - 62Data InquiryUse the Data Inquiry to request the current value for Parameters (i.e., ControlParameters or Monitor Parameters).Table 3-33 Data I

Pagina 176 - Index - 10

3 - 63Characters 5,6 - Parameter Number:This is the Control Parameter code (i.e., enter “16” for CP–16).Characters 7 through 10 - DATA:These character

Pagina 177 - Index - 11

3 - 64Table 3-34 Data Inquiry - ML-Drive ResponseCharacter # 1 2 3 4 5 6 7 8 9 10 11 12DEV # DEV # ERROR PAR # PAR # DATA DATA DATA DATA DATADESC ST

Pagina 178 - Index - 12

3 - 65Characters 5,6 - Parameter Number:The Control Parameter code is sent back to the host computer from the ML-Drive.Characters 7 through 10 - DATA:

Comentarios a estos manuales

Sin comentarios